Datalogic temperature controller temparature is going down is is a problem.
Hardware: Datalogic temperature controller ES-series
Software configuration:
Observation: when starting the machine, the controller displayed the ambient temperature. But then, the temperature displayed decreased to -50 degrees Celsius, after which 'UnFL' ('Underflow') was displayed.
Cause: the two-wire resistance thermometer is connected to the backside of the controller in the backwards order.
Solution: swap the wires connected to connectors 14 and 15.